As compared to a 2-wire D.C. distributor, a 3-wire distributor with same maximum voltage to earth uses only

31.25 percent of copper
33.3 percent of copper
distributor, a 3-wire distributor with same maximum voltage to earth uses only A. 31.25 percent of copper B. 33.3 percent of copper C. 66.7 percent of copper
125 percent of copper

The correct answer is A. 31.25 percent of copper.

A 2-wire D.C. distributor has two conductors, one for the positive voltage and one for the negative voltage. A 3-wire D.C. distributor has three conductors, one for the positive voltage, one for the negative voltage, and one for the ground. The ground conductor is used to provide a safe path for current to flow in the event of a fault.

The amount of copper used in a distributor is proportional to the square of the voltage. This means that a 3-wire distributor with the same maximum voltage to earth as a 2-wire distributor will use only 31.25% of the copper.

Option B is incorrect because it is the amount of copper used in a 3-wire distributor with twice the maximum voltage to earth. Option C is incorrect because it is the amount of copper used in a 2-wire distributor with twice the maximum voltage to earth. Option D is incorrect because it is the amount of copper used in a 3-wire distributor with four times the maximum voltage to earth.

Exit mobile version